OUTPUT
|
Output Volt Amp Capacity (VA) |
1000 |
Output kVA Capacity (kVA) |
1 |
Output Watt Capacity (Watts) |
900 |
Output kW Capacity (kW) |
0.9 |
Power Factor |
0.9 |
Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
Nominal Voltage Details |
230v nominal inverter output voltage |
Frequency Compatibility |
50 / 60 Hz |
Output Voltage Regulation (Line Mode) |
+6%, -11% |
Output Voltage Regulation (Battery Mode) |
+/- 5% |
Output Receptacles |
(6) C13 |
Included Output Power Cables |
Includes 2 C13 to C14 output power cables |
Load Management Receptacles |
Two switchable two-outlet C13 load banks |
Hot-Swap PDU options |
PDUBHV10 (2U / 8 C13 outlets) |
Output AC Waveform (AC Mode) |
Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |
|
INPUT
|
Rated input current (Maximum Load) |
4.8A |
Nominal Input Voltage(s) Supported |
230V AC |
UPS Input Connection Type |
C14 inlet |
UPS Input Connection Description |
IEC320-C14 input connection accepts a variety of user supplied detachable C13 output cordsets to match country or site-specific power sources |
Input Circuit Breakers |
10A |
Input Phase |
Single-Phase |
|
BATTERY
|
Full Load Runtime (min.) |
3.6 min. (900w) |
Half Load Runtime (min.) |
11.9 min (450w) |
DC System Voltage (VDC) |
24 |
Battery Recharge Rate (Included Batteries) |
Less than 4.5 hours from 10% to 90% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
See Tripp Lite RBC selector guide |
Battery Access |
Front panel battery access door |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Expandable Runtime |
No |
|
VOLTAGE REGULATION
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 182 to 278 |
Overvoltage Correction |
Input voltages between 244 and 278 are reduced by 12% |
Undervoltage Correction |
Input voltages between 182 and 206 are boosted by 12% |
|
USER INTERFACE, ALERTS & CONTROLS
|
Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) |
Switches |
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions |
Alarm Cancel Operation |
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available |
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
LED Indicators |
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status |
|
SURGE / NOISE SUPPRESSION
|
UPS AC Suppression Joule Rating |
350 |
UPS AC Suppression Response Time |
Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |
|
PHYSICAL
|
Included Mounting Accessory Description |
4 post rackmount installation accessories included |
Installation Form Factors Supported with Optional Accessories |
2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND); 2-4 post front rail rackmount(UPSHDEARKIT) |
Primary Form Factor |
Rackmount |
UPS Power Module Dimensions (hwd, cm) |
8.9 x 44.4 x 34.3 |
Rack Height (U Spaces) |
2 |
UPS Power Module Weight (kg) |
15.4 |
UPS Shipping Dimensions (hwd / cm) |
22.9 x 61 x 51.4 |
Shipping Weight (kg) |
16.3 |
Cooling Method |
Fan |
UPS Housing Material |
Steel |
|
ENVIRONMENTAL
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
100 |
AC Mode Efficiency Rating (100% Load) |
97% |
|
COMMUNICATIONS
|
Communications Interface |
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
Included |
Communications Cable |
USB and DB9 cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER
|
Transfer Time |
2-4 milliseconds |
Low Voltage Transfer to Battery Power (Setpoint) |
182 |
High Voltage Transfer to Battery Power (Setpoint) |
278 |
|
SPECIAL FEATURES
|
Grounding Lug |
Back panel grounding lug |
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
High Availability UPS Features |
Hot swappable batteries |
Green Energy-Saving Features |
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks |
|
CERTIFICATIONS
|
UPS Certifications |
CE; ROHS (Restriction of Hazardous Substances); Tested to GOST (Russia) |
UPS Certification Details |
IEC 62040-1, IEC 62040-2 Class A EMI |
|
WARRANTY
|
Product Warranty Period (International) |
2-year limited warranty |
Product Warranty Period (Mexico) |
2-year limited warranty |
Product Warranty Period (Puerto Rico) |
2-year limited warranty |
|