PLEASE NOTE: All prices are exclusive of GST │ Please call / email our sales team to get the updated product price and to check the stock availability before placing an order. If you do not find the product that you require or the prices are not available ($0) please send us an email/ call us so we can assist. *Sold out products can be made available upon request.
Cart 0
TrippLite OMNIVSINT800

TrippLite

TrippLite OMNIVSINT800


OmniVS 230V 800VA 475W Line-Interactive UPS, USB port, C13 Outlets

  • 800VA tower 230V line interactive UPS
  • Corrects brownouts as low as 159V without using battery power
  • USB port, TEL/DSL protection
  • C14 input and 4 C13 outlets

Features

  • OMNIVSINT800 Uninterruptible Power Supply offers voltage regulation, surge suppression and long lasting battery support
  • Supports entry level PCs up to 40 minutes during blackouts to enable shutdown without data loss
  • Regulates brownouts as low as 159 volts back to usable levels without using battery power
  • 4 IEC320 C13 outlets with complete AC surge suppression
  • C14 inlet accepts user-supplied AC power cord with country specific plug
  • USB port and cable enables unattended shutdown in the case of extended power failure
  • PowerAlert software available via free download from www.tripplite.com
  • Single line phone suppression protects standard dialup/DSL phone connection
  • Audible alarm and 4 front panel LEDs offer complete UPS and line power status information
  • 800VA power handling ability supports a variety of sensitive electronic equipment
  • 3.5 minutes full load runtime(800VA), 11.5 minutes half load runtime(400VA)
  • Supports battery replacement via built-in access panel
  • Optional PDUBHV10 bypass PDU enables hot-swappable UPS replacement with no disruption to connected equipment.

Specifications

OUTPUT
Output Volt Amp Capacity (VA) 800
Output Watt Capacity (Watts) 475
Nominal Output Voltage(s) Supported 220V; 230V; 240V
Nominal Voltage Details 230V inverter nominal voltage output
Frequency Compatibility 50 / 60 Hz
Output Voltage Regulation (Battery Mode) +/- 5%
Output Receptacles (4) C13
Included Output Power Cables Includes 2 C13 to C14 output power cables
Hot-Swap PDU options PDUBHV10 (2U / 8 C13 outlets)
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) PWM sine wave
INPUT
Rated input current (Maximum Load) 2.4A
Nominal Input Voltage(s) Supported 230V AC
UPS Input Connection Type C14 inlet
UPS Input Connection Description Attached 15cm line cord with C14 inlet. The C14 accepts a user-supplied AC power cord with country-specific plug.
UPS Input Cord Length (ft.) 0.5
UPS Input Cord Length (m) 0.2
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 3.5 min. (475w)
Half Load Runtime (min.) 11.5 min. (240w)
DC System Voltage (VDC) 12
Battery Recharge Rate (Included Batteries) Less than 4.5 hours from 10% to 90%
Internal UPS Replacement Battery Cartridge RBC51
Battery Access Battery access door
Battery Replacement Description Hot-swappable, user replaceable batteries
Expandable Runtime No
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with input voltage as low as 159
Undervoltage Correction Input voltages between 159 and 199 are boosted by 14%
USER INTERFACE, ALERTS & CONTROLS
Switches 2 Switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status
Audible Alarm Audible alarm indicates power-failure and low-battery conditions
LED Indicators 4 LEDs indicate line power, battery power, overload and battery low/replace status
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 340
UPS AC Suppression Response Time Instantaneous
UPS Dataline Suppression 1 line TEL/DSL (1 in / 1 out)
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Installation Form Factors Supported with Included Accessories Tower
Installation Form Factors Supported with Optional Accessories Wallmount(UPSWM - tower mounting kit)
Primary Form Factor Tower
UPS Power Module Dimensions (hwd, cm) 27.3 x 13.3 x 19
UPS Power Module Weight (kg) 8.9
UPS Shipping Dimensions (hwd / cm) 35.6 x 21.6 x 27.9
Shipping Weight (kg) 10.2
UPS Housing Material PVC
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 49.9
Battery Mode BTU / Hr. (Full Load) 455.5
AC Mode Efficiency Rating (100% Load) 97%
COMMUNICATIONS
Communications Interface USB
PowerAlert Software Free download from www.tripplite.com
Communications Cable USB interface cable included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time 2-4 milliseconds
Low Voltage Transfer to Battery Power (Setpoint) 159
SPECIAL FEATURES
Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
High Availability UPS Features Hot swappable batteries
Green Energy-Saving Features Greater than 95% efficiency - GREEN UPS
CERTIFICATIONS
UPS Certifications Tested to UL1778 (USA); CE; Tested to GOST (Russia); Tested to SASO (Saudi Arabia); Tested to IRAM (Argentina)
WARRANTY
Product Warranty Period (International) 2-year limited warranty
Product Warranty Period (Mexico) 2-year limited warranty
Product Warranty Period (Puerto Rico) 2-year limited warranty