OUTPUT
|
Output Volt Amp Capacity (VA) |
1500 |
Output kVA Capacity (kVA) |
1.5 |
Output Watt Capacity (Watts) |
900 |
Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
Nominal Voltage Details |
230v inverter nominal output voltage |
Frequency Compatibility |
50 / 60 Hz |
Output Voltage Regulation (Line Mode) |
-18%, +8% |
Output Voltage Regulation (Battery Mode) |
+/- 5% |
Output Receptacles |
(8) C13 |
Included Output Power Cables |
Includes 2 C13 to C14 output power cables. |
Hot-Swap PDU options |
PDUBHV10 (2U / 8 C13 outlets) |
Output AC Waveform (AC Mode) |
Sine wave |
Output AC Waveform (Battery Mode) |
PWM sine wave |
|
INPUT
|
Rated input current (Maximum Load) |
4.4A |
Nominal Input Voltage(s) Supported |
230V AC |
UPS Input Connection Type |
C14 inlet |
UPS Input Connection Description |
Attached 15cm line cord with C14 inlet. C14 inlet accepts user-supplied AC power cord with country specific plug. |
Input Circuit Breakers |
5.5A |
UPS Input Cord Length (ft.) |
0.5 |
UPS Input Cord Length (m) |
0.2 |
Input Phase |
Single-Phase |
|
BATTERY
|
Full Load Runtime (min.) |
4.5 min. (900w) |
Half Load Runtime (min.) |
12 min. (450w) |
DC System Voltage (VDC) |
24 |
Battery Recharge Rate (Included Batteries) |
Less than 4.5 hours from 10% to 90% |
Expandable Runtime |
No |
|
VOLTAGE REGULATION
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 144 to 282 |
Overvoltage Correction |
Input voltages between 245 and 282 are reduced by 12% |
Undervoltage Correction |
Input voltages between 177 and 199 are boosted by 14% |
Severe Undervoltage Correction |
Input voltages between 144 and 176 are boosted by 30% |
|
USER INTERFACE, ALERTS & CONTROLS
|
Front Panel LCD Display |
Backlighted LCD screen indicates input voltage, 5-bar battery charge level, overload, AVR, on battery and replace battery status; LCD screen rotates for rack/tower viewing |
Switches |
2 Switches control off/on power status and alarm-cancel/self-test operation |
Alarm Cancel Operation |
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status |
Audible Alarm |
Audible alarm indicates power-failure, low-battery and overload status; alarm can be disabled using PowerAlert software |
LED Indicators |
Front panel LCD display |
|
SURGE / NOISE SUPPRESSION
|
UPS AC Suppression Joule Rating |
890 |
UPS AC Suppression Response Time |
Instantaneous |
UPS Dataline Suppression |
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet; Coax jacks (1 set) |
EMI / RFI AC Noise Suppression |
Yes |
|
PHYSICAL
|
Included Mounting Accessory Description |
Pair of mounting ears enable tower and 2-4 post rackmount installation |
Installation Form Factors Supported with Included Accessories |
Tower |
Primary Form Factor |
Rackmount |
UPS Power Module Dimensions (hwd, cm) |
8.9 x 43.8 x 26.7 |
Rack Height (U Spaces) |
2 |
Maximum Device Depth (cm) |
26.7 |
UPS Power Module Weight (kg) |
13.3 |
UPS Shipping Dimensions (hwd / cm) |
19 x 57.2 x 38.7 |
Shipping Weight (kg) |
15.2 |
UPS Housing Material |
ABS |
|
ENVIRONMENTAL
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
127.5 |
Battery Mode BTU / Hr. (Full Load) |
540 |
AC Mode Efficiency Rating (100% Load) |
96% |
|
COMMUNICATIONS
|
Communications Interface |
USB (HID enabled); DB9 Serial |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
Free download from www.tripplite.com |
Communications Cable |
USB and DB9 Serial cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER
|
Transfer Time |
2-4 milliseconds |
Low Voltage Transfer to Battery Power (Setpoint) |
144 |
High Voltage Transfer to Battery Power (Setpoint) |
282 |
|
SPECIAL FEATURES
|
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
Green Energy-Saving Features |
Greater than 95% efficiency - GREEN UPS |
|
CERTIFICATIONS
|
UPS Certifications |
CE; Tested to GOST (Russia); Tested to SASO (Saudi Arabia); Meets FCC Part 15 Category A (EMI) |
UPS Certification Details |
CE IEC 62040-1-1, 62040-1-2 |
|
WARRANTY
|
Product Warranty Period (International) |
2-year limited warranty |
Product Warranty Period (Mexico) |
2-year limited warranty |
Product Warranty Period (Puerto Rico) |
2-year limited warranty |
|